Voltage Drop Calculator UK
Verify BS 7671 Regulation 525 compliance for electrical circuits in seconds — using official Table 4D1B mV/A/m values.
Quick answer
BS 7671 voltage drop limits: 3% for lighting, 5% for power circuits. Formula: VD = (mV/A/m × current × length) ÷ 1000. Use Table 4D1B values.
BS 7671 Voltage Drop Calculator
Table 4D1B mV/A/m method — copper conductors at 70°C
Values from BS 7671 Table 4D1B (PVC copper at 70°C)
⚡ Important Compliance Notes
- BS 7671 limits: 3% for lighting, 5% for other circuits (Regulation 525.1)
- Calculation method: Official Table 4D1B mV/A/m values at 70°C operating temperature
- Formula: VD = (mV/A/m × I × L) ÷ 1000 — do NOT multiply by 2
- mV/A/m values: Already account for both live and neutral conductors
- Three phase: Multiply single-phase result by 0.866 (√3/2)
- SWA cables: Use Table 4D4B values for armoured cables (separate calculator)
- Always consult: A qualified, registered electrician for installation work and complex scenarios. This calculator does not constitute professional electrical advice.
Voltage Drop Calculators by Application
Jump to a specific use-case calculator with pre-filled values for your scenario:
Submain to Outbuilding
Garden offices, garages, workshops, annexes
10mm²-25mm² SWA · 32A-63A
EV Charger Installation
7kW and 22kW home charging points
6mm²-10mm² · 32A continuous
Garden Lighting
Path lights, security lights, festoons
1.5mm²-2.5mm² · 3% lighting limit
Shower Circuit
8.5kW, 9.5kW, 10.5kW electric showers
6mm²-10mm² · 37A-46A
Cooker Circuit
Electric ovens, hobs, range cookers
6mm²-10mm² · 32A-45A with diversity
Three-Phase Motor
Industrial motors with 0.866 factor & starting current
Solar PV
Inverter to consumer unit AC cable sizing
Heat Pump
ASHP & GSHP circuits — MCS compliant
Marina Shore Power
Section 709 — stricter 3% limit applies
Caravan & Camping Site
Section 708 pitch supplies & PME considerations
Commercial Lighting
3% limit — offices, retail, emergency
Warehouse & Industrial
Long runs, three-phase distribution
Server Room / Data Centre
UPS feeds, critical power, 2-3% target
Agricultural & Farm
Section 705 — grain dryers, livestock
Swimming Pool
Section 702 — zones, SELV, bonding
Hot Tub & Spa
13A-32A dedicated outdoor circuits
Home Battery Storage
Tesla, GivEnergy, hybrid inverters
Workshop & Garage
Welders, compressors, machinery
Annex & Granny Flat
Separate dwelling supplies
Construction Site
Section 704 — temporary supplies
Ring Circuit
UK ring main — divide by 4 method
Radial Circuit
20A and 32A socket circuits
Domestic Lighting
Indoor lighting — 3% limit
Immersion Heater
3kW hot water circuits
12V DC Systems
Caravans, boats, solar, garden
SWA Armoured Cable
Buried and external cable runs
Underfloor Heating
Electric UFH mats and cables
Understanding Voltage Drop in Electrical Circuits
Voltage drop is the reduction in voltage that occurs as electrical current flows through cables due to conductor resistance. As current travels along a conductor, it encounters resistance which dissipates energy as heat and causes a voltage reduction at the load. BS 7671:2018+A2:2022 Regulation 525 sets strict limits on acceptable voltage drop to ensure electrical equipment operates safely and efficiently.
The phenomenon scales with three variables: the current flowing through the cable, the length of the cable run, and the cross-sectional area of the conductor. Larger cables have lower resistance per metre and therefore produce less voltage drop for the same current and length. This is why long runs to outbuildings, EV chargers, and electric showers often need substantially larger cable than the load current alone would suggest.
Key principle: Long cable runs with high current draw experience significant voltage drop. A 32A circuit running 30 metres in 2.5mm² cable: VD = (18 × 32 × 30) ÷ 1000 = 17.28V (7.5%) — this exceeds the 5% limit and requires larger cable.
BS 7671 Regulation 525 Voltage Drop Limits
According to Regulation 525.1, the voltage drop between the origin of the installation and any load point must not exceed specific percentages. These limits ensure equipment operates properly, safely, and reliably across the full range of normal operating conditions.
Lighting Circuits — 3% Maximum
Lighting is more sensitive to voltage reduction. At 3% drop (6.9V at 230V), LEDs and fluorescents dim noticeably. Best practice targets less than 2% for LED circuits.
Example: 230V × 3% = 6.9V maximum
Power & Other Circuits — 5% Maximum
Motors and appliances tolerate greater voltage drop but still require adequate voltage for proper operation and to prevent overheating during high-load periods.
Example: 230V × 5% = 11.5V maximum
Why Voltage Drop Matters
Excessive voltage drop is one of the most common causes of electrical installation failures. The consequences are serious and costly:
Effects of excessive voltage drop
- LED and fluorescent lights dim significantly
- Motors overheat and operate inefficiently
- Equipment malfunction or premature failure
- Reduced appliance lifespan due to thermal stress
- BS 7671 non-compliance
- EICR certification failures
- Costly remedial work after installation
Benefits of proper design
- Equipment operates at rated efficiency
- Longer equipment and cable lifespan
- Full compliance with BS 7671
- Passes EICR inspections first time
- Reduced operating costs over the install lifetime
- Customer satisfaction and fewer call-backs
How Voltage Drop is Calculated (BS 7671 Method)
This calculator uses the official BS 7671 method with mV/A/m values from Table 4D1B. These values are for thermoplastic (PVC) insulated copper conductors at 70°C operating temperature — the actual temperature cables reach under design current load.
Formula:
VD = (mV/A/m × I × L) ÷ 1000
- VD = Voltage drop in volts
- mV/A/m = Millivolts per amp per metre (from Table 4D1B)
- I = Design current in amps (Ib)
- L = Cable length in metres (one-way)
- 1000 = Conversion factor (mV to V)
Important: Do NOT multiply by 2 — the mV/A/m values already account for both conductors.
Practical example
A 20A circuit running 30 metres in 2.5mm² cable (18 mV/A/m):
VD = (18 × 20 × 30) ÷ 1000 = 10.8V (4.7%)
This exceeds the 3% lighting limit but passes for power circuits. For lighting, use 4mm² (11 mV/A/m): VD = 6.6V (2.87%) ✓
Common Voltage Drop Scenarios
Long cable runs to outbuildings
Garages, workshops, and garden buildings often require submains of 20–50 metres. Example: 32A at 40m with 10mm² (4.4 mV/A/m) = (4.4 × 32 × 40) ÷ 1000 = 5.63V (2.4%) ✓
Electric vehicle charging points
32A EV chargers draw continuous high current. 32A at 25m with 6mm² (7.3 mV/A/m) = (7.3 × 32 × 25) ÷ 1000 = 5.84V (2.5%) ✓
Large motors and air conditioning
High inductive loads have poor power factor and starting inrush currents 5–7× higher than running current. Calculate voltage drop for starting current to prevent equipment failure on start-up.
LED lighting in long runs
LED drivers are sensitive to low voltage. 6A at 20m with 1.5mm² (29 mV/A/m) = (29 × 6 × 20) ÷ 1000 = 3.48V (1.5%) ✓ — within 3% lighting limit.
63A submain circuits
63A circuits are common for large residential installations or substantial submains. 63A at 30m with 16mm² (2.8 mV/A/m) = (2.8 × 63 × 30) ÷ 1000 = 5.29V (2.3%) ✓
✓ Pass inspections & EICR every time
Verifying voltage drop compliance during the design phase saves costly remedial work. Use this calculator before installation to ensure your design passes certification first time. Document your calculations using Table 4D1B mV/A/m values to prove BS 7671 compliance to inspectors.
BS 7671 Table 4D1B — mV/A/m Reference
Voltage drop values for thermoplastic (PVC) insulated copper conductors at 70°C operating temperature. These values already include both conductors — do NOT multiply by 2.
| Cable Size (mm²) | mV/A/m | Typical Uses |
|---|---|---|
| 1.0 | 44 | Low-current single circuits |
| 1.5 | 29 | Lighting circuits |
| 2.5 | 18 | Ring finals, radial sockets |
| 4.0 | 11 | Immersion heaters, high-load radials |
| 6.0 | 7.3 | Cookers, showers up to 9kW |
| 10.0 | 4.4 | Large showers, small submains |
| 16.0 | 2.8 | Submains, long runs, 63A circuits |
| 25.0 | 1.75 | Main supplies, large submains |
| 35.0 | 1.25 | Heavy submains |
| 50.0 | 0.93 | Main feeds, commercial submains |
Source: BS 7671:2018+A2:2022 Table 4D1B — Voltage drop (mV/A/m) for single-phase circuits. For three-phase, multiply result by 0.866.
Glossary of Terms
- mV/A/m
- Millivolts per amp per metre — the unit BS 7671 Table 4D1B uses to express voltage drop characteristics of a cable. Multiply by current and length, then divide by 1000 to get voltage drop in volts.
- BS 7671
- The British Standard for electrical installations, also known as the IET Wiring Regulations. The current edition is BS 7671:2018 incorporating Amendment 2:2022. Sets requirements for safe electrical installations in the UK.
- Regulation 525
- The specific clause within BS 7671 that sets maximum permitted voltage drop limits — 3% for lighting circuits, 5% for other circuits.
- Table 4D1B
- The reference table in BS 7671 Appendix 4 that lists mV/A/m values for thermoplastic (PVC) insulated copper conductors operating at 70°C, used to calculate voltage drop.
- Design current (Ib)
- The current the circuit is designed to carry under normal operating conditions. Used as the input for voltage drop calculations alongside cable length and size.
- EICR
- Electrical Installation Condition Report — a periodic inspection of an electrical installation's safety. Excessive voltage drop is a common cause of EICR failure.
- CCC
- Current-Carrying Capacity — the maximum current a cable can safely carry without exceeding its temperature rating. One of three sizing checks alongside voltage drop and disconnection time.
- PVC copper
- Thermoplastic (polyvinyl chloride) insulated copper conductor — the most common cable type in UK installations. Operating temperature 70°C.
- Three-phase factor
- The 0.866 multiplier (√3/2) applied to single-phase mV/A/m values when calculating three-phase voltage drop. Reflects the balanced nature of three-phase loads.
- Origin of the installation
- The point where the consumer's installation begins — typically the meter tails entering the consumer unit. Voltage drop is measured from here to the furthest load point.
Frequently Asked Questions
What are BS 7671 voltage drop limits?
BS 7671 Regulation 525 limits voltage drop to 3% for lighting circuits and 5% for other circuits including power, heating, and motors. These are measured from the origin of the installation to any load point. On a 230V single-phase supply, this means 6.9V maximum for lighting and 11.5V maximum for power.
How is voltage drop calculated using BS 7671 Table 4D1B?
For single phase circuits: VD = (mV/A/m × current × length) ÷ 1000. For three phase: VD = (mV/A/m × current × length × 0.866) ÷ 1000. The mV/A/m values from Table 4D1B already account for both conductors at 70°C operating temperature, so do NOT multiply by 2. This is the official BS 7671 method.
Why does voltage drop matter?
Excessive voltage drop causes equipment malfunction, motor overheating, LED dimming, reduced equipment lifespan, and BS 7671 non-compliance. Proper calculation during the design phase prevents costly installation failures and EICR certification failures.
What if my voltage drop calculation exceeds the limit?
You have three options. First, increase the cable size to reduce the mV/A/m value — going from 2.5mm² (18 mV/A/m) to 4mm² (11 mV/A/m) cuts voltage drop by 39%. Second, reposition the distribution board closer to the load to shorten the run. Third, split a large load across multiple smaller circuits.
Why don't you multiply by 2 when using mV/A/m values?
The mV/A/m values in BS 7671 Table 4D1B already account for both conductors (live and neutral) at the cable's actual 70°C operating temperature. The older "multiply resistance by 2" method uses conductor resistance at 20°C, which is a different approach and underestimates real-world voltage drop by approximately 20%. Don't mix methods — use mV/A/m without the factor of 2.
Does the 3% or 5% limit apply to the whole installation or just final circuits?
The limit applies to the TOTAL voltage drop from the origin of the installation (typically the consumer unit or distribution board) to the load point. This includes distribution circuits AND final circuits combined. You cannot exceed 3% for lighting or 5% for power as a total.
How does three-phase voltage drop differ from single phase?
Three-phase circuits have inherently lower voltage drop because the load is balanced across three conductors. The formula uses a 0.866 factor (√3/2) to convert single-phase tabulated mV/A/m values, and the percentage is calculated against 400V line-to-line rather than 230V single phase.
Does this calculator work for SWA armoured cable?
The default calculator uses BS 7671 Table 4D1B which covers thermoplastic (PVC) insulated copper conductors. SWA cables use Table 4D4B with slightly different mV/A/m values. For most domestic SWA submains the difference is small, but for precise compliance work consult Table 4D4B directly. We have a dedicated SWA Armoured Cable calculator that uses the correct values.
Can I temporarily exceed voltage drop limits during motor starting?
BS 7671 recognises that transient voltage drops during motor starting (where inrush current is typically 5–7× running current) are acceptable if they don't cause equipment damage or hazardous operation. However, design should still minimise starting inrush voltage drop. Continuous operation must meet the stated 3% or 5% limits.
How do I account for future load growth in my design?
Design for anticipated future maximum demand rather than current load. This avoids costly cable upgrades later. For example, if a distribution board might eventually need 40A, design for 40A now rather than upgrading from 20A in five years' time. Voltage drop scales linearly with current, so over-sizing the cable today saves significant disruption later.
Do I need to apply temperature correction to mV/A/m values?
No. The Table 4D1B values are already at 70°C operating temperature. Unlike the conductor resistance method which uses 20°C and needs correction, mV/A/m values represent real operating conditions under design current load.
Is this calculator compliant with the 18th Edition?
Yes. All calculations follow BS 7671:2018+A2:2022 Regulation 525 requirements and use mV/A/m values from Table 4D1B for thermoplastic (PVC) insulated copper conductors at 70°C operating temperature. The methodology matches what a qualified electrician would use during design.
Does voltage drop include the supply cable from the DNO cutout?
No. BS 7671 voltage drop is measured from the origin of the installation (typically the consumer unit or distribution board) to the load. The DNO supply cable from the substation to the cutout has its own permitted drop separately under ESQCR (Electricity Safety, Quality and Continuity Regulations).
Can I use this calculator for EV charger and heat pump circuits?
Yes. EV chargers and heat pumps are power circuits subject to the 5% voltage drop limit. Both typically have long runs from the consumer unit, making voltage drop a critical sizing factor. Use the actual continuous design current — 32A for a 7.4kW EV charger, or the heat pump nameplate rating. We have dedicated EV Charger and Heat Pump calculators with pre-filled scenarios.
Is voltage drop the same as cable sizing?
No. Voltage drop is one of three checks for cable sizing under BS 7671. The other two are current-carrying capacity (the cable must safely carry the design current without overheating) and disconnection time under fault conditions. A fully compliant cable size satisfies all three checks. This calculator handles voltage drop only — verify CCC and disconnection time separately.
Built by TradeCalcs — automation tools for UK trades, part of Autaimate. Calculations verified against BS 7671:2018+A2:2022 Table 4D1B mV/A/m values for thermoplastic (PVC) insulated copper conductors at 70°C operating temperature. This calculator does not constitute professional electrical advice — always consult a registered, qualified electrician for installation work. Last reviewed: 29 April 2026.
Complete Your Electrical Design
Voltage drop is one of three BS 7671 sizing checks. Use these companion calculators to verify the full design:
Want a Bespoke Calculator or App?
Are you a contractor or business looking for custom calculation tools, quote generators, or workflow apps built specifically for your trade? Tell us what you need and we'll be in touch.
Start your enquiryOr email us directly: mick@tradecalcs.co.uk